2-pair plug-in surge protector
E280-TM
Part Number: 71186
- 2-pair plug-in module
- Optimized modularity and maintenance
- Can be adapted to all types of line
- Gas tube /diode combination
- UL497A
The E280 concept is based on the use of plug-in module to protect telecom and data lines.
The E280 line covers all multi-line telephone and data installation configurations: there is an E280 module and a suitable support for every type.
Each module protects two pairs and is available for all types of line. The plug-in concept makes maintenance easy and lest you mix different types of line on the same support.
Select another reference:
Network | RTC, ADSL, SDSL, SHDSL | |
Nominal line voltage | Un | 150 V |
Max. DC operating voltage | Uc | 170 V |
Max. frequency | f max. | > 10 MHz |
Insertion loss | < 1 dB | |
Max. load current | IL | 300 mA |
Max. discharge current | Imax | 10 kA |
Total Maximum discharge current | Imax Total | 20 kA |
Line inductance | No | |
Protection mode(s) | Common/Differential mode | |
Protection level | Up | 220 V |
Max. capacitance | C | < 70 pF |
Impulse current | Iimp | 2.5 kA |
Nominal discharge current | In | 5 kA |
Type of diagram | A |
Technology | GDT+Clamping diode | |
SPD configuration | 2 pairs | |
Format | plug-in modul on support | |
Mounting | on support type BN, FPSU, MMP | |
Housing material | Thermoplastic UL94 V-0 | |
Operating temperature | Tu | -40/+85°C |
Protection rating | IP20 | |
Failsafe mode | Short-circuit - transmision cut-off - fault mode 2 | |
Disconnection indicator | Transmission interrupt | |
Remote signaling of disconnection | No | |
Dimensions | See diagram |
Standards compliance | IEC 61643-21 / EN 61643-21 / UL497A | |
Certification | UL listed |