CITEL
Test Facilities
Jobs & Career
About us
Locations
GTC
Lightning Surges
Citel's VG Technology
International Standards
Lightning and Transient overvoltages
The origin of overvoltages
Keraunic levels
Effects of lightning
Surge Protection
Products
AC Power
Radiocommunication
Telecom
Miscellaneous
GDT
Dataline
Photovoltaic
LED
Applications
Security Systems
Wind Turbine Installation
Industrial Installation
Datacenter
Surge protection for LED-lighting systems
Photovoltaic installations
Gas Discharge Tubes and Gas Filled Spark Gaps
Surge protection for E-mobility
Surge protection for cell phone communication
Water treatment
Services
Information
Order form
Selection guide
Partner
Toggle Dropdown
Contact Citel
Privacy policy
Our partners in Europe
Impress
Toggle Dropdown
News
Contact
Product ranges
AC Power
Photovoltaic
LED
Telecom
Dataline
Radiocommunication
GDT
Accessories
AC Power
Type 2 (or 3) AC surge protector
DS14S-120/G
Type 2 (or 3) AC surge protector - 3-phase+N
DS14S-120/G
Part Number:
471632
Type 2 (or 3) AC Multipolar surge protector
In : 5 kA
Imax total: 40 kA
Pluggable module by phase
Remote signaling
EN 61643-11, IEC 61643-11, UL1449 ed.5 compliance
Datasheet
Installation Sheet
Tender specifications
Contact Us
DS10 type2 AC surge protector are used mainly for primary protection of single and 3- phase networks at the main electrical panel. They provide common-mode or common and differential mode. This SPD is based on high energy varistor equipped with thermal disconnector and failure indicator, to comply with standards. The DS10 surge protectors are designed to be used in a multipolar configuration to protect single-phase, 3-phase or 3-phase+Neutral AC networks.They are sometimes associated with dedicated N/PE surge protector based on gas tube technology.
Select another reference:
DS11S-120
DS11S-230
DS11S-400
DS12S-120
DS12S-120/G
DS12S-230
DS12S-230/G
DS12S-400
DS13S-120
DS13S-230
DS13S-400
Electrical Properties
Mechanical Properties
Norms
Deconnector
Schemas
SPD type
2 (or 3)
Network
120/208 V 3-phase+N
AC system
TT-TNS
Nominal line voltage
Un
120 Vac
Max. AC operating voltage
Uc
150 Vac
Temporary Over Voltage (TOV) Charasteristics - 5 sec.
UT
180 Vac withstand
Temporary Over Voltage (TOV) Charasteristics - 120 mn
UT
230 Vac disconnection
Temporary Over Voltage N/PE (TOV HT)
UT
1200 V/300A/200 ms withstand
Residual Current
Ipe
None
Operating current
Ic
0.5 mA
Follow current
If
None
Nominal discharge current
In
5 kA
Max. discharge current
Imax
10 kA
Total Maximum discharge current
Imax Total
40 kA
Withstand on Combination waveform IEC 61643-11
Uoc
10 kV
Withstand on overvoltages IEEE C62.41.1
10 kV
Connection mode(s)
L/N and N/PE
Protection mode(s)
Common/Differential mode
Protection level L/N
Up L/N
0.6 kV
Admissible short-circuit current
Isccr
25 000 A
Technology
MOV+GDT
SPD configuration
3-phase+Neutral
Connection to Network
By screw terminals: 2.5-25mm² / by bus
Format
Plug-in modular box
Mounting
Symmetrical rail 35 mm (EN 60715)
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu
-40/+85°C
Protection rating
IP20
Failsafe mode
Disconnection from AC network
Disconnection indicator
1 mechanical indicator by pole
Spare module(s)
DSM10-120 + DSM40G-600
Remote signaling of disconnection
Output on changeover contact
Dimensions
See diagram
Weight
0.320 kg
Standards compliance
IEC 61643-11 / EN 61643-11 / UL1449 ed.5
Certification
UL Recognized
Thermal disconnector
Internal
Installation ground fault breaker
Type 'S' or delayed
Fuses
20 A min. - 125 A max. - Fuses type gG
×
Read more