Type 1+2 AC surge protector - 1-pole

DS250E-48DC
Part Number 63909
DS250E-48DC
  • 2-poles surge protector 48 Vdc
  • Type 1 and Type 2 application
  • In 25 kA / Imax 70 kA
  • Remote signaling
  • Iimp 25 kA
  • IEC 61643-11 and EN 61643-11 compliance

DS250E-48DC surge protectors are designed to protect equipment connected to DC power supplies from lightning surges

Select another reference:

SPD type
IEC

1+2

Network

48 Vdc

Nominal line voltage
Un

48 Vdc

Nominal DC voltage
Un-dc

48 Vdc

Max. DC operating voltage
Uc

75 Vdc

Residual Current
Leakage current to Ground
Ipe

< 0.2 mA

Operating current
Continious current at Uc
Ic

< 0.1 mA

Follow current
If

None

Nominal discharge current
15 x 8/20 µs impulses
In

25 kA

Max. discharge current
max. withstand @ 8/20 µs by pole
Imax

70 kA

Total Maximum discharge current
max. total withstand @ 8/20 µs
Imax Total

140 kA

Impulse current by pole
max. withstand 10/350µs by pole
Iimp

25 kA

Specific energy by pole
max. withstand 10/350 µs
W/R

156 kJ/ohm

Connection mode(s)

+/PE or -/PE

Protection mode(s)

Common mode

Protection level +/PE (-/PE)
@ In (8/20µs)
Up

500 V

Technology

MOV

SPD configuration

Single phase

Connection to Network

By screw terminals: 6-35mm² / by bus

Format

1-pole modular box

Mounting

Symmetrical rail 35 mm (EN 60715)

Housing material

Thermoplastic UL94 V-0

Operating temperature
Tu

-40/+85°C

Protection rating

IP20

Failsafe mode

Disconnection from DC network

Disconnection indicator

3 mechanical indicators

Remote signaling of disconnection

Output on changeover contact

Wiring for remote signaling

1.5 mm² max.

Max. Voltage/Current for remote signaling

250 V / 0.5 A (AC) / 30 V / 3 A (DC)

Dimensions

See diagram

Weight

0.25 kg

Standards compliance

IEC 61643-11 / EN 61643-11 / UL1449 ed.5

Certification
Thermal disconnector

Internal

Back-up protection device

Fuses type gG - 315 A