DC power surge protector
Part Number: 828511263
DDC50S-21Y-500
- DC power Type 2 SPD
- For Energy Storage/EV Charging
- In/Imax: 20/50 kA
- Pluggable modules
- Remote signaling
- prIEC 61643-41 compliance
The DDC50S-21Y range is type 2 pluggable surge protectors designed for protection to Energy System Storage (ESS).
Its technology based on high energy varistor equipped with thermal disconnection mechanism offers protection efficiency and and a maximal reliability.
These DC power surge protectors are available with a Max. DC operating voltage from 500 to 1500 Vdc.
To ensure maximum protection of the ESS installation, CITEL has developed a kit (article code: 1156339601) of products consisting of a DDC50S-21Y surge protector and a specific fuse (100,000 A tested and approved) compatible with: short-circuits of storage systems and CITEL surge protectors.
|
SPD type
|
IEC | 2 |
|
Nominal DC voltage
|
Un-dc | 450 Vdc |
|
Max. DC operating voltage
|
Uc | 500 Vdc |
|
Residual Current
Leakage current to Ground
|
Ipe | < 0.2 mA |
|
Nominal discharge current
15 x 8/20 µs impulses
|
In | 20 kA |
|
Max. discharge current
max. withstand @ 8/20 µs by pole
|
Imax | 50 kA |
|
Impulse current by pole
max. withstand 10/350µs by pole
|
Iimp | 4 kA |
|
Protection level +/-
@ In (8/20µs)
|
Up | 2.1 kV |
|
Admissible short-circuit current
|
Isccr | 100 000 A |
|
Connection to Network
|
By screw terminals: 2.5-25 mm² (35 mm² rigid) |
|
|
Plugable
|
Yes |
|
|
Mounting
|
Symmetrical rail 35 mm (EN 60715) |
|
|
Housing material
|
Thermoplastic UL94 V-0 |
|
|
Operating temperature
|
Tu | -40/+85°C |
|
Protection rating
|
IP20 |
|
|
Failsafe mode
|
Disconnection from DC network |
|
|
Disconnection indicator
|
1 mechanical indicator by pole - Red/Green |
|
|
Spare module(s)
|
MDDC50-500 |
|
|
Remote signaling of disconnection
|
output on changeover contact |
|
|
Wiring for remote signaling
|
1.5 mm² max. |
|
|
Max. Voltage/Current for remote signaling
|
250 V / 0.5 A (AC) / 30 V / 3 A (DC) |
|
|
Dimensions
|
See diagram - 3 TE (EN43880) |
|
|
APPLICATION
|
ENERGY STORGAGE SYSTEMS (ESS) /EV CHARGING |
|
Standards compliance
|
prIEC 61443-41 - IEC61643-11 |
|
|
Environmental standards
|
EU RoHS |
|
Thermal disconnector
|
Internal |
|
|
Back-up protection device
|
50 A min. (Isccr 100 kA) - 125 A max. (Isccr 50 kA) - gBat Fuses |
Datasheet