Coaxial surge protector DC-3.5 GHz

Part Number: 60001

Lightning Protection Zones (LPZ)

0 - 3

Max. DC operating voltage
Uc

72 Vdc

Frequency range
f

DC-3.5 GHz

Insertion loss

< 0.2 dB

Return loss

> 20 dB

Impedance

50 ohms

VSWR

<1.2:1

Max. load current @25°C
IL

10 A

Residual Current
Leakage current to Ground
Ipe

None

Max. discharge current
max. withstand @ 8/20 µs by pole
Imax

20 kA

Nominal discharge current
C2 (1.2/50us / 8/20µs), 10 applications X-C (Line/Earth)
In

10 kV / 5 kA

Protection Level
C2 (1.2/50µs / 8/20µs), 10 applications, Y-C (Line-Earth)
Up

< 1000 V

Protection Level
C3 (10/1000μs), 300 applications@10 A, Y-C (Line/Earth)
Up

< 700 V

Impulse current
D1 (10/350μs), 2 applications, X-C (Line/Earth)
Iimp

500 A

Max RF Power

25 W

Typical let through energy
(50 ohms) input 4kV 1.2/50μs - 2kA 8/20μs

300 µJ

DC Pass

Yes

Insulation resistance
IR

≥10 GOhms

Technology

Gas discharge tube

Connection to Network

Connector N Male/Female

Mounting

Bulkhead or Bracket

Housing material

Brass/Surface plating: Cu Zn Sn

Operating temperature
Tu

-40/+85°C

Relative Humidity

5 - 85%

Ingress Protection rating

IP65 (NEMA 4)

Failsafe mode

Transmision cut-off - fault mode 2 (short circuit)

Disconnection indicator

Transmision interrupt

Spare module(s)

BBHF-90V

Dimensions

See diagram

Contacts

Bronze/Surface Au-Ag

Standards compliance

IEC 61643-21 / EN 61643-21 / UL497E

UL Category

QVLA - Antenna lead-in conductors

UL File Number

E349646

Environmental standards

EU RoHS