Junction boxes
Part Number: 159147
AK1.K5x16.K5x16.13VGS-31-275
- Universal small housing for individual cable entry with consideration of practical cross-sections
- Internal terminal design allows spur or V-wiring (series)
- Suitable for TN-TT mains types
- Integrated DAC13VGS-31-275
- Type 1+2+3 combined arrester based on a gas-filled spark gap
- Discharge capacity per pole: Iimp= 12,5 kA (10/350μs); Imax= 50kA (8/20μs)
- Pluggable protection modules
- Remote signalling as standard
- Can be used for lightning protection classes III + IV
- VDE-AR-N 4100 compliant "Use of surge protective devices (SPD) type 1 in main power supply systems"
|
SPD type
|
IEC | 1+2+3 |
|
Nominal line voltage
|
Un | 230/400 Vac |
|
Max. AC operating voltage
|
Uc | 275 Vac |
|
Max. load current
if series connection
|
IL | bis 76 A (Verlegeart beachten) |
|
Surge protection device
|
DAC1-13VGS-31-275 (internally pre-wired) |
|
|
Nominal frequency
|
fn | 0-100 Hz |
|
Housing material
|
Thermoplastic UL94 V-0 |
|
|
Protection rating
|
IP65 |
|
|
Dimensions
|
See diagram - 3 TE (EN43880) |
|
|
Entrance
|
Screw terminals max. 16mm² (re or rm) |
|
|
Outgoing
|
Screw terminals max. 16mm² (re or rm) |
|
|
Earth connection terminal
|
Screw terminals max. 16mm² (re or rm) |
|
|
Ambient temperature
|
-25°C bis +40°C / 24h up to max. 35°C |
|
|
Cable gland
|
Double diaphragm connector Cable glands M20 / M25 / M32 |
|
|
Humidity
|
Relative humidity (25°C) 5% to 95% / Max. relative air humidity (40°C) 50%. |
|
|
Shock resistance
|
IK 08 |
|
Standards compliance
|
IEC 61643-11 |
Datasheet