Type 1+2+3 AC surge protector - 3-phase

ZPAC1-13VG-30-275
Part Number 64215
ZPAC1-13VG-30-275
  • Type 1+2+3 combined SPD based on a gas-filled spark gap
  • 10-year guarantee
  • Discharge capacity per pole: Iimp= 12.5 kA (10/350 μs)
  • Safe disconnecting device
  • Operating and leakage current-free
  • Can be used for lightning protection classes III + IV
  • Cost-effective maintenance thanks to individual plug-in modules
  • Complies with the IEC 61643-11 and EN 61643-11 standards
  • Complies with VDE-AR-N 4100 “Use of surge protective devices (SPD) type 1 in main power supply systems”

The ZPAC1-13VG-30-275 with 12.5kA discharge capacity per pole is a space-saving and cost-effective solution for buildings with lightning protection classes III+IV and is designed for installation on 40 mm busbar systems. Thanks to the integrated CITEL VG technology, the ZPAC1-13VG-30-275, like the DS253VG-300 as a type 1+2+3 combined SPD, combines all three protection classes in one device and thus offers very good protection against surges for the downstream system. It also meets the minimum requirements for type 1 lightning current SPD in accordance with VDE 0100-534 with a required discharge capacity of 12.5kA (10/350). The ZPAC1-13VG-30-275 fulfills the VDN guideline for lightning protection class III+IV and can therefore be used in the pre-metering area. This makes the ZPAC ideally suited for installation in private and commercial buildings.


SPD type
IEC

1+2+3

Network

230/400 V 3-phase

AC system

TNC

Nominal line voltage
Un

230/400 Vac

Max. AC operating voltage
Uc

275 Vac

Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
UT

335 Vac withstand

Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
UT

440 Vac withstand

Residual Current
Leakage current to Ground
Ipe

None

Operating current
Continious current at Uc
Ic

None

Follow current
If

None

Nominal discharge current
15 x 8/20 µs impulses
In

20 kA

Max. discharge current
max. withstand @ 8/20 µs by pole
Imax

50 kA

Impulse current by pole
max. withstand 10/350µs by pole
Iimp

12.5 kA

Total lightning current
max. total withstand @ 10/350µs
Itotal

37.5 kA

Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
Uoc

6 kV

Specific energy by pole
max. withstand 10/350 µs
W/R

40 kJ/ohm

Protection mode(s)

L/PE

Protection level L/PE
@ In (8/20µs)
Up L/PE

1.5 kV

Residual voltage L/PE at 5 kA
@ 5 kA (8/20µs)
Up-5kA

0.9 kV

Admissible short-circuit current
Isccr

50 000 A

Technology

VG Technology (MOV+GSG)

SPD configuration

3-phase

Connection to Network

By 40mm busbar and wire for PE: 6-35mm² (50mm²)

Format

Plug-in modular box

Mounting

40 mm busbar systems

Housing material

Thermoplastic UL94 V-0

Operating temperature
Tu

-40/+85°C

Protection rating

IP20

Outdoor application

No

Failsafe mode

Disconnection from AC network

Disconnection indicator

1 mechanical indicator by pole

Spare module(s)

MDAC1-13VG-275

Remote signaling of disconnection

none

Dimensions

See diagram

Weight

0.677 kg

Standards compliance

IEC 61643-11 / EN 61643-11 / UL1449 5ed.

Certification

KEMA

Thermal disconnector

Internal

Installation ground fault breaker

Type 'S' or delayed

Back-up protection device

max. 315 A (gL/gG)