Compact 1-phase Type 2 (or 3) surge protector - 120 V -Pluggable
DS240S-280
Part Number: 311121
- Compact single-phase Type 2 surge protector
- In : 20 kA
- Imax : 40 kA
- Common mode
- Pluggable module
- Remote signaling
- EN 61643-11, CEI 61643-11 compliance
- UL1449 ed.6
The DS240 Type 2 surge protectors are compact devices designed to protect single phase networks at the main switchboard.
They provide a common or common/differential mode protection.
This SPD is based on high energy varistor equipped with thermal disconnectors and failure indicator to comply with standards.
The DS240 is DIN rail compatible and is built with a plug-in module and fixed base, which allows an easy and fast maintenance.
Select another reference:
SPD type | 2 | |
Network | 230 V single-phase | |
AC system | TN | |
Nominal line voltage | Un | 230 Vac |
Max. AC operating voltage L-N | Uc | 280 Vac |
Max. load current | IL | 20 A |
Temporary Over Voltage (TOV) Charasteristics - 5 sec. | UT | 335 Vac withstand |
Temporary Over Voltage (TOV) Charasteristics - 120 mn | UT | 440 Vac disconnection |
Residual Current | Ipe | < 0.5 mA |
Follow current | If | None |
Nominal discharge current | In | 20 kA |
Max. discharge current | Imax | 40 kA |
Total Maximum discharge current | Imax Total | 80 kA |
Connection mode(s) | L/PE and N/PE | |
Protection mode(s) | Common mode | |
Residuel voltage at 5 kA | Up-5kA | 0.9 kV |
Protection level CM/DM | Up mc/md | 1.3 kV |
Admissible short-circuit current | Isccr | 10 000 A |
Technology | MOV | |
SPD configuration | Single phase | |
Connection to Network | by screw terminals: 1.5-10mm² (L/N) or 2.5-25mm² (PE) | |
Format | Plug-in modular box | |
Mounting | Symmetrical rail 35 mm (DIN 60715) | |
Housing material | Thermoplastic UL94-V0 | |
Operating temperature | Tu | -40/+85°C |
Protection rating | IP20 | |
Failsafe mode | Disconnection | |
Disconnection indicator | 2 mechanical indicators | |
Spare module(s) | DSM240-280 | |
Remote signaling of disconnection | Output on changeover contact | |
Dimensions | See diagram |
Standards compliance | IEC 61643-11 / EN 61643-11 / UL1449 4ed. | |
Certification | UL / EAC / TUV |
Thermal disconnector | Internal | |
Installation ground fault breaker | Type 'S' or delayed | |
Fuses | Fuses type gG - 50 A |