Type 2 (or 3) AC surge protector - one-phase
DS11S-120
Part Number: 341611
- Type 2 (or 3) AC one-phase surge protector
- In : 5 kA
- Imax : 10 kA
- Pluggable module by phase
- Remote signaling
- EN 61643-11, CEI 61643-11, UL1449 ed.4 compliance
DS10 type2 AC surge protector are used mainly for primary protection of single and 3- phase networks at the main electrical panel.
They provide common-mode or common and differential mode.
This SPD is based on high energy varistor equipped with thermal disconnector and failure indicator, to comply with standards.
The DS10 surge protectors are designed to be used in a multipolar configuration to protect single-phase, 3-phase or 3-phase+Neutral AC networks.They are sometimes associated with dedicated N/PE surge protector based on gas tube technology.
Select another reference:
SPD type | 2 (or 3) | |
Network | 120/208 V | |
Nominal line voltage | Un | 120 Vac |
Max. AC operating voltage | Uc | 150 Vac |
Temporary Over Voltage (TOV) Charasteristics - 5 sec. | UT | 180 Vac withstand |
Temporary Over Voltage (TOV) Charasteristics - 120 mn | UT | 230 Vac disconnection |
Residual Current | Ipe | < 0.5 mA |
Operating current | Ic | 0.5 mA |
Follow current | If | None |
Nominal discharge current | In | 5 kA |
Max. discharge current | Imax | 10 kA |
Total Maximum discharge current | Imax Total | 10 kA |
Withstand on Combination waveform IEC 61643-11 | Uoc | 10 kV |
Withstand on overvoltages IEEE C62.41.1 | 10 kV | |
Connection mode(s) | L/N or N/PE | |
Protection mode(s) | Common Mode or Differential Mode | |
Protection level | Up | 0.6 kV |
Admissible short-circuit current | Isccr | 25000 A |
Technology | MOV | |
SPD configuration | 1-pole | |
Connection to Network | By screw terminals: 2.5-25 mm² / by bus | |
Format | Plug-in modular box | |
Mounting | Symmetrical rail 35 mm (DIN 60715) | |
Housing material | Thermoplastic UL94 V-0 | |
Operating temperature | Tu | -40/+85°C |
Protection rating | IP20 | |
Failsafe mode | Disconnection | |
Disconnection indicator | 1 mechanical indicator | |
Spare module(s) | DSM10-120 | |
Remote signaling of disconnection | Output on changeover contact | |
Dimensions | See diagram |
Standards compliance | IEC 61643-11 / EN 61643-11 / UL1449 4ed. | |
Certification | UL / EAC / TUV |
Thermal disconnector | Internal | |
Installation ground fault breaker | Type 'S' or delayed | |
Fuses | 20 A min. - 125 A max. - Type gG |