Surge protectors for LED lighting system Class 2
MLP2-230L-P/DL
Part Number 721232
- Type 2 or 3 surge protector for 2-phase (Power/Control)
- For LED lighting system
- Class I configuration
- IP65 version
- Very compact dimensions
- Max. discharge current 10kA
- EN 61643-11, IEC 61643-11 compliance
The MLP range is a comprehensive series of AC surge protectors
dedicated to LED lighting system. Some versions are
equipped with an extra dataline surge protection (RS485 or
DALI) in order to provide a full solution for LED systems with
transmission features. By this way the MLP range is able to provide
all the existing configurations with an efficient solution .
MLP surge protectors are based on a powerful association of
MOV and GDT components, able to protect LED system against
huge surges without disconnection.
In the worse case, the SPD will fail in safety condition. Indication
of the SPD failure is performed through power supply cut off
and/or through remote signaling feature.
Select another reference:
SPD type
|
IEC | 2+3 |
AC system
|
TT-TN | |
Nominal line voltage
|
Un | 230-277 Vac |
Max. AC operating voltage
|
Uc | 305 Vac |
Max. frequency
|
f max. | 10 MHz |
Max. load current @25°C
|
IL | 2.5 A |
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
|
UT | 335 Vac withstand |
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
|
UT | 440 Vac disconnection |
Residual Current
Leakage current to Ground
|
Ipe | None |
Follow current
|
If | None |
Nominal discharge current
15 x 8/20 µs impulses
|
In | 5 kA |
Max. discharge current
max. withstand @ 8/20 µs by pole
|
Imax | 10 kA |
Total Maximum discharge current
max. total withstand @ 8/20 µs
|
Imax Total | 20 kA |
Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
|
Uoc | 10 kV / 5 kA |
Withstand on overvoltages IEEE C62.41.1
|
10 kV / 10 kA | |
Protection mode(s)
|
Common/Differential mode | |
Protection level L/N
@ In (8/20µs)
|
Up L/N | 1.5 kV |
Protection level L/PE
@ In (8/20µs)
|
Up L/PE | 1.5 kV |
Admissible short-circuit current
|
Isccr | 10 000 A |
Network type
|
AC/Data | |
Mounting
|
Wall or plate | |
Housing material
|
Thermoplastic UL94 V-0 | |
Operating temperature
|
Tu | -40/+85°C |
Dimensions
|
See diagram |
Standards compliance
|
IEC 61643-11 / EN 61643-11 / UL1449 ed.5 |
Thermal disconnector
|
Internal | |
Installation ground fault breaker
|
Type 'S' or delayed |