Surge protector for LED lighting system Class 1

DLPM1-230L/Y
Part Number 355923
DLPM1-230L/Y
  • Type 2 (or 3) surge protectors for LED
  • For single-phase or biphase network
  • Very compact (low profile)
  • DIN rail mounting
  • Screw terminal connection
  • Mechanical status indicator
  • Disconnection AC end of life
  • EN 61643-11 compliance

The DLPM range is a series of DIN-mount AC surge protector designed to be installed inside the cutouts: his compact size and lower height make it compatible with the DIN rail mounting of its enclosures. This range has a mechanical disconnect indicator.


SPD type
IEC 2 (or 3)
Network
220-240 Vac Single-phase or biphase network
AC system
TN
Nominal line voltage
Un 230-277 Vac
Max. AC operating voltage
Uc 320 Vac
Max. load current @25°C
IL 10 A
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
UT 335 Vac withstand
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
UT 440 Vac disconnection
Temporary Over Voltage N/PE (TOV HT)
Without disconnection or with safety disconnection
UT 1200 V/300A/200 ms breaker disconnection
Residual Current
Leakage current to Ground
Ipe None
Operating current
Continious current at Uc
Ic None
Nominal discharge current
15 x 8/20 µs impulses
In 5 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 10 kA
Total Maximum discharge current
max. total withstand @ 8/20 µs
Imax Total 20 kA
Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
Uoc 10 kV / 5 kA
Withstand on overvoltages IEEE C62.41.1
10 kV / 10 kA
Protection mode(s)
Common/Differential mode
Protection level L/N
@ In (8/20µs)
Up L/N 1.5 kV
Protection level L/PE
@ In (8/20µs)
Up L/PE 1.5 kV
Admissible short-circuit current
Isccr 10 000 A
Technology
MOV+GDT
Connection to Network
Screw terminal 2.5 mm² max. Earthing conductor 2 mm² - length 60 cm
Mounting
Symmetrical rail 35 mm (EN 60715)
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu -40/+85°C
Protection rating
IP20
Failsafe mode
Disconnection from AC network
Disconnection indicator
1 mechanical indicator
Voltage/operating indicator
Green Indicator
Remote signaling of disconnection
No
Dimensions
See diagram
Weight
0.068 kg
Standards compliance
EN 61643-11 / IEC 61643-11
Thermal disconnector
Internal
Installation ground fault breaker
Type 'S' or delayed