Protection against Surge, Temporary and Permanent overvoltages for Class II LED lighting system
MLPVM2-230L-5A
Part Number 832278
- Protection against all types of overvoltages
- For Class II Led lighting
- 230 V single-phase network / 5 A
- Function 'Surge voltage protection' (SPD)
- Surges due to lighting or switching
- Function 'Permanent or temporary overvoltage protection' (POP)
The MLPVM has been designed to protect single-phase Class 2 equipment. This product offers protection against transient overlvoltage and a protection against temporary and permanent overvoltage on the network. The MLPVM complies IEC 61643-11 standards. The MLPVM offers a very good power ratio with a discharge capacity of 10 kA and a very compact format. The installation of the product is done via its spring terminals.
Select another reference:
Network
|
230 V single-phase | |
AC system
|
TT-TN | |
Max. AC operating voltage
|
Uc | 255 Vac |
Max. load current @25°C
|
IL | 5 A |
Residual Current
Leakage current to Ground
|
Ipe | None |
Nominal discharge current
15 x 8/20 µs impulses
|
In | 5 kA |
Max. discharge current
max. withstand @ 8/20 µs by pole
|
Imax | 10 kA |
Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
|
Uoc | 10 kV |
Withstand on overvoltages IEEE C62.41.1
|
10 kV / 10 kA | |
Protection mode(s)
|
L/N | |
Protection level L/N
@ In (8/20µs)
|
Up L/N | 1.5 kV |
Admissible short-circuit current
|
Isccr | 10 000 A |
Connection to Network
|
In series by conductors 1.5mm² - spring terminal | |
Mounting
|
On plate | |
Housing material
|
Thermoplastic UL94 V-0 | |
Operating temperature
|
Tu | -40/+85°C |
Protection rating
|
IP20 | |
Insulation class
|
Classe 2 | |
Failsafe mode
|
Disconnection and AC line cut-off | |
Disconnection indicator
|
Green LED OFF and line cut off | |
Voltage/operating indicator
|
Green Led ON | |
Dimensions
|
See diagram | |
Weight
|
0.040 kg |
Standards compliance
|
EN 61643-11 / IEC 61643-11 | |
Certification
|