Ultra Compact Type 2+3 hard wired surge protector

MLPX2VG-230L-W
Part Number 711292
MLPX2VG-230L-W
  • Ultra compact Type 2+3 hard wired surge protectors
  • Class 2
  • Wall mounting and hard wired connection
  • VG Technology
  • No aging
  • Bracket breakable
  • Protection rating : IP67
  • Disconnection signaling by indicator
  • AC disconnection in case of end of life
  • EN 61643-11, IEC 61643-11 and UL1449 4ed. compliance



SPD type
2+3
Network
230-277 V Single-phase
AC system
TT-TN
Nominal line voltage
Un 230 V
Max. AC operating voltage
Uc 320 Vac
Max. load current
@25°C
IL 10 A
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
UT 335 Vac withstand
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
UT 440 Vac withstand
Temporary Over Voltage N/PE (TOV HT)
Without disconnection or with safety disconnection
UT 1200 V/300A/200 ms disconnection
Residual Current
Leakage current to Ground
Ipe None
Nominal discharge current
15 x 8/20 µs impulses
In 5 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 10 kA
Total Maximum discharge current
max. total withstand @ 8/20 µs
Imax Total 20 kA
Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
Uoc 10 kV
Withstand on overvoltages IEEE C62.41.1
10 kV / 10 kA
Protection mode(s)
Differential Mode
Protection level L/N
@ In (8/20µs)
Up L/N 1.5 kV
Admissible short-circuit current
Isccr 10 000 A
Technology
MOV+GDT
Connection to Network
By wires: 1.5mm² (L/N) and 2.5mm² (PE)
Mounting
Wall or plate
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu -40/+85°C
Protection rating
IP67
Failsafe mode
Disconnection and AC line cut-off
Disconnection indicator
LED green OFF and AC network cut-off
Voltage/operating indicator
Green Led ON
Dimensions
See diagram
Standards compliance
IEC 61643-11 / EN 61643-11 / UL1449 ed.5
Certification
Thermal disconnector
Internal
Installation ground fault breaker
Type 'S' or delayed