PV-DC-Junction box
Part Number: 158575
CiPlug2-51-12
- Generator junction box for 2 MPP tracker / 1 strings
- Integrated surge protection (DS50PVS-1000G/12KT1, Type 1+2)
- Protection class IP65
- Connection via MC4-connectors
With the new CiPlug string box, CITEL is providing a solution to protect the DC side of small and medium-sized Photovoltaic (PV) systems against the effects of surges and overvoltages. With its small dimensions, the CiPlug is ideal for rooftop installations in the residential building sector.
The CiPlug includes pre-assembled pv-cables equipped with MC4 plugs, which enables a very fast and easy installation. With its maximum system voltage (Ucpv) of 1200 Vdc, it is applicable for any common configuration and reliably protects the MPP tracker of the inverter.
Depending on the configuration, the CiPlug meets the normative requirements for all types of buildings with or without external lightning protection system up to lightning protection class I (Iimp = 12.5 kA / pole (10/350)).
|
SPD type
|
IEC | 1+2 |
|
Network
|
PV network 1000 Vdc |
|
|
Nominal DC voltage
|
Un-dc | 1000 Vdc |
|
Max. PV operating voltage
|
Ucpv | 1200 Vdc |
|
Rated insulation voltage
Ui
|
Ui | 1000 Vdc |
|
Rated current
InA
|
InA | 2x 20 A |
|
Rated string current
|
InC | 2x 20 A |
|
Housing material
|
UV and ozone resistant, glass fibre reinforced polycarbonate |
|
|
Dimensions
|
See diagram |
|
|
Input / per MPPT
|
MC4 plug 1x 6mm² with 15cm connection cable |
|
|
Output / per MPPT
|
MC4-Stecker 1x 6mm² mit 120cm Anschlussleitung |
|
|
Ground connection terminal
|
Screw terminal 2.5-25mm² (35mm²) |
|
|
Cable gland
|
Metric / 2x M24 (Ø 6-12mm) PE |
|
|
Housing material
|
UV and ozone resistant, fiberglass reinforced polycarbonate with semi-transparent cover |
|
|
Dimensions
|
WxHxD (mm): 300 x 200 x 132 |
|
|
Ambient temperatures
|
Indoor: -5°C to max. +40°C (+35°C 24h average) / Outdoor: -25°C to max. +40°C (+35°C 24h average) |
|
|
Humidity
|
Indoor: max. 50% at +40°C, max. 90% at 20°C (non-condensing) / Outdoor: 95% for a short time at +25°C (non-condensing) |
|
|
Protection rating
|
IP 65 |
|
|
Protection class
|
Class II |
|
|
Impact resistance
|
IK 8 |
|
|
Pressure compensation element
|
Existing |
|
Standards compliance
|
DIN EN 50539-11 / DIN EN IEC 61439-2 |
Datasheet