PV-DC-Junction box

CiPlug2-51VG-12
Part Number 158572
CiPlug2-51VG-12
  • Generator junction box for 2 MPP tracker / 1 strings
  • Integrated surge protection (DS50VGPVS-1000G/12KT1, Type 1+2)
  • Protection class IP65
  • Connection via MC4-connectors

With the new CiPlug string box, CITEL is providing a solution to protect the DC side of small and medium-sized Photovoltaic (PV) systems against the effects of surges and overvoltages. With its small dimensions, the CiPlug is ideal for rooftop installations in the residential building sector. The CiPlug includes pre-assembled pv-cables equipped with MC4 plugs, which enables a very fast and easy installation. With its maximum system voltage (Ucpv) of 1200 Vdc, it is applicable for any common configuration and reliably protects the MPP tracker of the inverter. Depending on the configuration, the CiPlug meets the normative requirements for all types of buildings with or without external lightning protection system up to lightning protection class I (Iimp = 12.5 kA / pole (10/350)).


SPD type
IEC

1+2

Network

PV network 1000 Vdc

Nominal DC voltage
Un-dc

1000 Vdc

Max. PV operating voltage
Ucpv

1200 Vdc

Rated insulation voltage
Ui
Ui

1000 Vdc

Rated current
InA
InA

2x 20 A

Rated string current
InC

2x 20 A

Housing material

UV and ozone resistant, glass fibre reinforced polycarbonate

Dimensions

See diagram

Input / per MPPT

MC4 plug 1x 6mm² with 15cm connection cable

Output / per MPPT

MC4-Stecker 1x 6mm² mit 120cm Anschlussleitung

Ground connection terminal

Screw terminal 2.5-25mm² (35mm²)

Cable gland

Metric / 2x M24 (Ø 6-12mm) PE

Housing material

UV and ozone resistant, fiberglass reinforced polycarbonate with semi-transparent cover

Dimensions

WxHxD (mm): 300 x 200 x 132

Ambient temperatures

Indoor: -5°C to max. +40°C (+35°C 24h average) / Outdoor: -25°C to max. +40°C (+35°C 24h average)

Humidity

Indoor: max. 50% at +40°C, max. 90% at 20°C (non-condensing) / Outdoor: 95% for a short time at +25°C (non-condensing)

Protection rating

IP 65

Protection class

Class II

Impact resistance

IK 8

Pressure compensation element

Existing

Standards compliance

DIN EN 50539-11 / DIN EN IEC 61439-2