PV-DC-Junction box
Part Number: 158207
GAK2.K4(6)x16.K2x16.51VG-1
- Generator junction box for 2 MPP tracker / 4 strings
- Integrated surge protection device (2x DS50VGPVS-1000G/51, type 2)
- Protection class IP65
- Connection via spring terminals
With the generator junction boxes of the GAK2 series, CITEL offers a solution to protect photovoltaic systems of any kind against the effects of lightning and overvoltages. The GAK2 series is designed to protect 2 MPP trackers and maximum system voltages (Ucpv) up to 1200 Vdc. Depending on the configuration, the GAK2 meet the normative requirements for all types of buildings with or without external lightning protection system up to lightning protection class I (Iimp = 12.5 kA / pole (10/350)) and are also available in versions with string fuses and disconnectors.
|
SPD type
|
IEC | 2 |
|
Network
|
PV network 1000 Vdc |
|
|
Nominal DC voltage
|
Un-dc | 1000 Vdc |
|
Max. PV operating voltage
|
Ucpv | 1200 Vdc |
|
Rated insulation voltage
Ui
|
Ui | 1000 Vdc |
|
Rated current
InA
|
InA | 2x 60 A |
|
Rated string current
|
InC | 2x 40 A |
|
Protection rating
|
IP65 |
|
|
Input / per MPPT
|
Spring clamp terminals / 4x16mm² |
|
|
Output / per MPPT
|
Spring terminals / 2x16mm² |
|
|
Ground connection terminal
|
Spring clamp terminals / 16mm² |
|
|
Cable gland
|
Metric / 30x M16 (Ø 5-7mm) |
|
|
Housing material
|
UV and ozone resistant, fiberglass reinforced polycarbonate with semi-transparent cover |
|
|
Dimensions
|
WxHxD (mm): 360 x 254 x 111 |
|
|
Ambient temperatures
|
Indoor: -5°C to max. +40°C (+35°C 24h average) / Outdoor: -25°C to max. +40°C (+35°C 24h average) |
|
|
Humidity
|
Indoor: max. 50% at +40°C, max. 90% at 20°C (non-condensing) / Outdoor: 95% for a short time at +25°C (non-condensing) |
|
|
Protection class
|
Class II |
|
|
Impact resistance
|
IK 8 |
|
|
Pressure compensation element
|
Existing |
|
Standards compliance
|
DIN EN 50539-11 / DIN EN IEC 61439-2 |
Datasheet