CITEL
About us
Locations
Test Facilities
Jobs & Career
GTC
Lightning Surges
Lightning and Transient overvoltages
The origin of overvoltages
Keraunic levels
Effects of lightning
Surge Protection
Citel's VG Technology
CITEL CTC-Technology
International Standards
Products
AC Power
Photovoltaic
LED
Dataline
Radiocommunication
Telecom
GDT
Miscellaneous
Applications
Datacenter
Surge protection for LED-lighting systems
Surge protection for cell phone communication
Security Systems
Industrial Installation
Wind Turbine Installation
Surge protection for photovoltaic systems
Water treatment
Surge protection for E-mobility
Surge protection for meter locations
Services
Information
Selection guide
Order form
Partner
Toggle Dropdown
Contact Citel
Our partners in Europe
Privacy policy
Impress
Toggle Dropdown
News
Contact
Product ranges
AC Power
Photovoltaic
LED
Telecom
Dataline
Radiocommunication
image/svg+xml
Wind Turbine
Accessories
Photovoltaic
Type 1+2+3 PV surge protector
DPVN1-6CVGS-21Y-1500
Type 1+2+3 PV surge protector - CTC Technology
DPVN1-6CVGS-21Y-1500
Part Number
65222103
NEW CITEL PV SPD
Type 1+2+3 surge protector for Photovoltaic
CTC Technology
VG Technology
Impulse currents Iimp/Itotal: 6.25/12.5 kA (10/350µs)
Common/Differential mode protection
Remote signaling
IEC 61643-31, EN 61643-31, EN 50539-11, UL1449 ed.5 compliance
Datasheet
Installation Sheet
Tender specifications
Contact Us
The DPVN1-VG is CITEL's new series of type '1+2+3' SPDs for photovoltaic applications. The development of these SPDs is based on two technologies, patented exclusively by CITEL. The 'VG Technology' guarantees total absence of leakage current and maximum reliability. Using 'CTC Technology', the DPVN1 incorporates a thermosensitive separation point placed at the center of the SPD, guaranteeing the safest disconnection on the market. The products are designed for DIN rail mounting. Compact and equipped with a fault indicator, these products are easy to install and maintain.
Select another reference:
DPVN1-6CVGS-21Y-1200
DPVN1-6CVGS-21Y-1500
Electrical Properties
Mechanical Properties
Norms
Deconnector
Schemas
SPD type
1+2+3
Network
PV 1500 Vdc
Nominal PV voltage
Uocstc
1250 Vdc
Max. PV operating voltage
Ucpv
1500 Vdc
Residual Current
Leakage current to Ground
Ipe
None
PV Permanent Operating current
Current consumption at Ucpv
Icpv
None
Follow current
If
None
Nominal discharge current
15 x 8/20 µs impulses
In
20 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax
40 kA
Total Maximum discharge current
max. total withstand @ 8/20 µs
Imax Total
60 kA
Impulse current by pole
max. withstand 10/350µs by pole
Iimp
6.25 kA
Total lightning current
max. total withstand @ 10/350µs
Itotal
12.5 kA
Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
Uoc
6 kV
Current withstand short circuit PV
Iscpv
15 000 A
Connection mode(s)
+/-/PE
Protection mode(s)
Common/Differential mode
Protection level +/-
@ In (8/20µs)
Up
4.8 kV
Protection level +/PE (-/PE)
@ In (8/20µs)
Up
4.8 kV
Technology
VG Technology (MOV+GSG)
Connection to Network
By screw terminals: 2.5-25mm² (35mm²) / by bus
Format
Compact monobloc box
Plugable
No
Mounting
Symmetrical rail 35 mm (EN 60715)
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu
-40/+85°C
Protection rating
IP20
Outdoor application
No
Failsafe mode
All pole disconnection from PV network
Disconnection indicator
1 mechanical indicator - Red/Green
Remote signaling of disconnection
Output on changeover contact
Max. Voltage/Current for remote signaling
250 V / 0.5 A (AC) / 30 V / 3 A (DC)
Dimensions
See diagram - 2.5TE (EN43880)
Weight
0.510 kg
Standards compliance
IEC 61643-31 / EN 61643-31 / EN 50539-11 / UL1449 ed.5
Thermal disconnector
CTC Technology integrated
Back-up protection device
Without
×
Description:
Type 1+2+3 PV surge protector - CTC Technology
Standards compliance:
IEC 61643-31 / EN 61643-31 / EN 50539-11 / UL1449 ed.5
Technology:
VG Technology (MOV+GSG)
Remote signaling of disconnection:
Output on changeover contact
SPD type :
1+2+3
Network:
PV 1500 Vdc
Max. PV operating voltage:
1500 Vdc
Residual Current :
None
Max. discharge current :
40 kA
Total Maximum discharge current :
60 kA
Impulse current by pole :
6.25 kA
CITEL
Reference:
DPVN1-6CVGS-21Y-1500
Part Number:
65222103
Or equivalent