Type 1+2 AC surge protector - 1-pole

DS250VG-1000
Part Number 64013
DS250VG-1000
  • Type 1+2 surge protector
  • In : 30 kA
  • Iimp : 25 kA
  • Low voltage Up
  • Internal disconnection, status indicator
  • Remote signaling
  • IEC 61643-11, EN 61643-11 and UL1449 ed4 compliance

The DS250VG-1000 AC surge protector is designed for 3-phase 1000 VAC and mainly use for wind generator networks,


SPD type
1+2
Nominal line voltage
Un 900 V
Max. AC operating voltage
Uc 1000 Vac
Max. load current
@25°C
IL 100 A
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
UT 1320 Vac withstand
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
UT 1732 Vac withstand
Residual Current
Leakage current to Ground
Ipe None
Follow current
If None
Nominal discharge current
15 x 8/20 µs impulses
In 30 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 60 kA
Impulse current by pole
max. withstand 10/350µs by pole
Iimp 25 kA
Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
Uoc 6 kV
Specific energy by pole
max. withstand 10/350 µs
W/R 156 kJ/ohm
Protection level
@ In (8/20µs)
Up < 3.4 kV
Admissible short-circuit current
Isccr 50 000 A
Technology
VG Technology (MOV+GSG)
SPD configuration
Single phase
Connection to Network
By screw: 6-35mm² (50mm² flexible)
Format
1-pole modular box
Mounting
Symmetrical rail 35 mm (EN 60715)
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu -40/+85°C
Protection rating
IP20
Failsafe mode
Disconnection from AC network
Disconnection indicator
1 mechanical indicator
Remote signaling of disconnection
Output on changeover contact
Dimensions
See diagram - 5 TE, DIN 43880
Weight
0.68 kg
Standards compliance
IEC 61643-11 / EN 61643-11 / UL1449 ed.5
Certification
Thermal disconnector
Internal
Installation ground fault breaker
Type 'S' or delayed
Back-up protection device
Fuses type gG - 315 A