CITEL
About us
Locations
Test Facilities
Jobs & Career
GTC
Lightning Surges
Lightning and Transient overvoltages
The origin of overvoltages
Keraunic levels
Effects of lightning
Surge Protection
Citel's VG Technology
CITEL CTC-Technology
International Standards
Products
AC Power
Photovoltaic
LED
Dataline
Radiocommunication
Telecom
GDT
Miscellaneous
Applications
Datacenter
Surge protection for LED-lighting systems
Surge protection for cell phone communication
Security Systems
Industrial Installation
Wind Turbine Installation
Surge protection for photovoltaic systems
Water treatment
Surge protection for E-mobility
Surge protection for meter locations
Services
Information
Selection guide
Order form
Partner
Toggle Dropdown
Contact Citel
Our partners in Europe
Privacy policy
Impress
Toggle Dropdown
News
Contact
Product ranges
AC Power
Photovoltaic
LED
Telecom
Dataline
Radiocommunication
image/svg+xml
Wind Turbine
Accessories
AC Power
Type 1+2 AC surge protector
DS252VG-1000
Type 1+2 AC surge protector - 1-pole
DS252VG-1000
Part Number
64014
Type 1+2 surge protector
In : 30 kA
Iimp : 25 kA
Low voltage Up
Internal disconnection, status indicator
Remote signaling
IEC 61643-11, EN 61643-11 and UL1449 ed4 compliance
Datasheet
Installation Sheet
Tender specifications
Contact Us
The DS250VG-1000 AC surge protector is designed for 3-phase 1000 VAC and mainly use for wind generator networks,
Select another reference:
DS250VG-1000
DS252VG-1000
DS253VG-1000
DS254VG-1000
Electrical Properties
Mechanical Properties
Norms
Deconnector
Schemas
SPD type
1+2+3
Network
1000 V Single Phase
AC system
TN
Nominal line voltage
Un
900 V
Max. AC operating voltage
Uc
1000 Vac
Max. load current
@25°C
IL
100 A
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
UT
1320 Vac withstand
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
UT
1732 Vac withstand
Residual Current
Leakage current to Ground
Ipe
None
Follow current
If
None
Nominal discharge current
15 x 8/20 µs impulses
In
30 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax
60 kA
Total Maximum discharge current
max. total withstand @ 8/20 µs
Imax Total
160 kA
Impulse current by pole
max. withstand 10/350µs by pole
Iimp
25 kA
Total lightning current
max. total withstand @ 10/350µs
Itotal
50 kA
Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
Uoc
6 kV
Specific energy by pole
max. withstand 10/350 µs
W/R
156 kJ/ohm
Protection level
@ In (8/20µs)
Up
4.0 kV
Residual voltage at 5 kA
@ 5 kA (8/20µs)
Up-5kA
2.6 kV
Admissible short-circuit current
Isccr
50 000 A
Technology
VG Technology (MOV+GSG)
SPD configuration
Single phase
Connection to Network
By screw: 6-35mm² (50mm² flexible)
Format
1-pole modular box
Mounting
Symmetrical rail 35 mm (EN 60715)
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu
-40/+85°C
Protection rating
IP20
Failsafe mode
Disconnection from AC network
Disconnection indicator
1 mechanical indicator
Remote signaling of disconnection
Output on changeover contact
Dimensions
See diagram - 10TE, DIN 43880
Weight
1.4 kg
Standards compliance
IEC 61643-11 / EN 61643-11 / UL1449 ed.5
Thermal disconnector
Internal
Installation ground fault breaker
Type 'S' or delayed
Back-up protection device
Fuses type gG - 315 A
×
Description:
Type 1+2 AC surge protector - 1-pole
Standards compliance:
IEC 61643-11 / EN 61643-11 / UL1449 ed.5
Technology:
VG Technology (MOV+GSG)
SPD configuration:
Single phase
Remote signaling of disconnection:
Output on changeover contact
SPD type :
1+2+3
Network:
1000 V Single Phase
AC system:
TN
Max. AC operating voltage :
1000 Vac
Residual Current :
None
Max. discharge current :
60 kA
Total Maximum discharge current :
160 kA
Impulse current by pole :
25 kA
Protection level :
4.0 kV
Admissible short-circuit current:
50 000 A
CITEL
Reference:
DS252VG-1000
Part Number:
64014
Or equivalent
Read more