Type 1+2 AC surge protector - 1-pole

DS250VG-690
Part Number 63162
DS250VG-690
  • Type 1+2 surge protector
  • For 400/690 V network
  • In: 30 kA
  • Iimp: 25 kA
  • Low voltage Up
  • Internal disconnection, status indicator
  • Remote signaling
  • UL1449 ed.5 compliance
  • IEC 61643-11, EN 61643-11 certified

The DS250VG-690 AC surge protector is designed for 3-phase 690VAC and mainly use for wind generator networks. The `Spark gap + Varistor` technology allows a very low level of protection and an absence of following current. The DS250VG-690 is mounted on a DIN Rail and has a double connection for the active conductor, which allows an optimized connection to the network. These AC surge protectors are designed to be connected in multi-pole configuration to protect single-phase, and 3-phase.

Select another reference:

SPD type
1+2
Network
400/690 V
Nominal line voltage
Un 690 Vac
Max. AC operating voltage
Uc 760 Vac
Max. load current
if series connection
IL 100 A
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
UT 1050 Vac withstand
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
UT 1350 Vac withstand
Residual Current
Leakage current to Ground
Ipe None
Follow current
If None
Nominal discharge current
15 x 8/20 µs impulses
In 30 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 100 kA
Impulse current by pole
max. withstand 10/350µs by pole
Iimp 25 kA
Withstand on overvoltages IEEE C62.41.1
20 kV
Specific energy by pole
max. withstand 10/350 µs
W/R 156 kJ/ohm
Connection mode(s)
L/N or L/PE
Protection mode(s)
Common Mode or Differential Mode
Protection level L/PE
@ In (8/20µs)
Up L/PE 4 kV
Residual voltage L/PE at 5 kA
@ 5 kA (8/20µs)
Up-5kA 2.6 kV
Admissible short-circuit current
Isccr 50 000 A
Technology
VG Technology (MOV+GSG)
SPD configuration
Single phase
Connection to Network
By screw: 6-35mm² (50mm² flexible)
Format
1-pole modular box
Mounting
Symmetrical rail 35 mm (EN 60715)
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu -40/+85°C
Protection rating
IP20
Failsafe mode
Disconnection from AC network
Disconnection indicator
1 mechanical indicator
Remote signaling of disconnection
Output on changeover contact
Dimensions
See diagram
Weight
0.68 kg
Standards compliance
IEC 61643-11 / EN 61643-11 / UL1449 ed.5
Certification
TUV
Thermal disconnector
Internal
Installation ground fault breaker
Type 'S' or delayed
Back-up protection device
Fuses type gG - 315 A