Type 1+2 AC surge protector - 3-phase+N
Part Number: 3732
DS254E-400
- Type 1 + 2 unipolar surge protector
- Iimp total: 100 kA on 10/350µs impulse
- Imax : 140 kA on 8/20µs impulse
- Internal disconnections, status indicators
- Remote signaling
- IEC 61643-11, EN 61643-11 and UL1449 ed.5 compliance
The DS250E is an extreme duty Type 1+2 designed to protect the entrance of the electrical installation.
They are used to protect biphase, 3-phase or 3-phase + neutral networks in common mode or in common and differential mode.
The 'Multi-Varistor' technology used allows the best possible behavior for the LV network (no follow-on current).
The DS250E is mounted on a DIN Rail and has a double connection for the active conductor, which allows an optimized connection to the network.
Certificates
|
SPD type
|
IEC | 1+2 |
|
Network
|
230/400 V 3-phase+N |
|
|
AC system
|
IT |
|
|
Nominal line voltage
|
Un | 230/400 Vac |
|
Max. AC operating voltage
|
Uc | 440 Vac |
|
Max. load current
if series connection
|
IL | 100 A |
|
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
|
UT | 580 Vac withstand |
|
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
|
UT | 770 Vac disconnection |
|
Residual Current
Leakage current to Ground
|
Ipe | < 3 mA |
|
Follow current
|
If | None |
|
Nominal discharge current
15 x 8/20 µs impulses
|
In | 50 kA |
|
Max. discharge current
max. withstand @ 8/20 µs by pole
|
Imax | 140 kA |
|
Impulse current by pole
max. withstand 10/350µs by pole
|
Iimp | 25 kA |
|
Total lightning current
max. total withstand @ 10/350µs
|
Itotal | 100 kA |
|
Specific energy by pole
max. withstand 10/350 µs
|
W/R | 156 kJ/ohm |
|
Connection mode(s)
|
L/PE and N/PE |
|
|
Protection mode(s)
|
Common mode |
|
|
Protection level N/PE
@ In (8/20µs)
|
Up N/PE | 2.5 kV |
|
Protection level L/PE
@ In (8/20µs)
|
Up L/PE | 2.5 kV |
|
Admissible short-circuit current
|
Isccr | 50 000 A |
|
Technology
|
MOV |
|
|
SPD configuration
|
3-phase+Neutral |
|
|
Connection to Network
|
By screw terminals: 6-35mm² / by bus |
|
|
Format
|
1-pole modular box assembled |
|
|
Mounting
|
Symmetrical rail 35 mm (EN 60715) |
|
|
Housing material
|
Thermoplastic UL94 V-0 |
|
|
Operating temperature
|
Tu | -40/+85°C |
|
Protection rating
|
IP20 |
|
|
Failsafe mode
|
Disconnection from AC network |
|
|
Disconnection indicator
|
3 mechanical indicators by pole |
|
|
Remote signaling of disconnection
|
Output on changeover contact |
|
|
Dimensions
|
See diagram |
|
Standards compliance
|
IEC 61643-11 / EN 61643-11 / UL1449 ed.5 |
|
|
Certification
|
|
Thermal disconnector
|
Internal |
|
|
Installation ground fault breaker
|
Type 'S' or delayed |
|
|
Back-up protection device
|
Fuse assembly: SFD1-25-40S / or Fuses Type gG 315 A |
Datasheet