Type 1+2 AC surge protector 3-phase

DS253E-400
Part Number 3939
DS253E-400
  • Type 1 + 2 unipolar surge protector
  • Iimp total: 75 kA on 10/350µs impulse
  • Imax : 140 kA on 8/20µs impulse
  • Internal disconnections, status indicators
  • Remote signaling
  • IEC 61643-11, EN 61643-11 and UL1449 ed.5 compliance

The DS250E is an extreme duty Type 1+2 designed to protect the entrance of the electrical installation. They are used to protect biphase, 3-phase or 3-phase + neutral networks in common mode or in common and differential mode. The 'Multi-Varistor' technology used allows the best possible behavior for the LV network (no follow-on current). The DS250E is mounted on a DIN Rail and has a double connection for the active conductor, which allows an optimized connection to the network.


SPD type
IEC 1+2
Network
230/400 V 3-phase
AC system
IT
Nominal line voltage
Un 400 Vac
Max. AC operating voltage
Uc 440 Vac
Max. load current
if series connection
IL 100 A
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
UT 580 Vac withstand
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
UT 770 Vac disconnection
Residual Current
Leakage current to Ground
Ipe < 3 mA
Follow current
If None
Nominal discharge current
15 x 8/20 µs impulses
In 50 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 140 kA
Impulse current by pole
max. withstand 10/350µs by pole
Iimp 25 kA
Total lightning current
max. total withstand @ 10/350µs
Itotal 75 kA
Specific energy by pole
max. withstand 10/350 µs
W/R 156 kJ/ohm
Connection mode(s)
L/PE
Protection mode(s)
Common mode
Protection level L/PE
@ In (8/20µs)
Up L/PE 2.5 kV
Admissible short-circuit current
Isccr 50 000 A
Technology
MOV
SPD configuration
3-phase
Connection to Network
By screw terminals: 6-35mm² / by bus
Format
1-pole modular box assembled
Mounting
Symmetrical rail 35 mm (EN 60715)
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu -40/+85°C
Protection rating
IP20
Failsafe mode
Disconnection from AC network
Disconnection indicator
3 mechanical indicators by pole
Remote signaling of disconnection
Output on changeover contact
Dimensions
See diagram
Weight
1.023 kg
Standards compliance
IEC 61643-11 / EN 61643-11 / UL1449 ed.5
Certification
Thermal disconnector
Internal
Installation ground fault breaker
Type 'S' or delayed
Back-up protection device
Fuse assembly: SFD1-25-30S / or Fuses Type gG 315 A