Isolating spark gap (ISG)

SGP40
Part Number 690102
SGP40
  • Isolating spark gap
  • Indoor application
  • Max. discharge current : 40 kA
  • EN 50164-3, IEC 62561-3 compliance

These spark gap are designed to protect metallic elements, like antennas, poles, pipes, roofing equipment…which are not connected to earth for operating reason, against the risk of flashover during strike on the installation. BFP100 is a specific version of the high energy gas tube P100, featured with isolated sleeve for outdoor application.

Select another reference:

Rated DC withstand voltage
Uw DC 500 V
Rated AC withstand voltage
Uw AC 300 V
DC sparkover voltage (100V/s)
600-900 V
Maximum impulse sparkover voltage (1kV/µs)
< 1500 V
Follow current
If Yes
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 40 kA
Impulse current by pole
max. withstand 10/350µs by pole
Iimp 15 kA
Classification following IEC 62561-3
2L
Insulation resistance
IR 1 Gohm
Rated impulse sparkover voltage
1kV/µs
Ur Iimp 1500 V
Technology
Gas discharge tube
Connection to Network
Threaded rod M10
Operating temperature
Tu -40/+85°C
Protection rating
IP54
Outdoor application
No
Dimensions
See diagram
Weight
0.14 kg
Standards compliance
EN 62561-3