CITEL
About us
Locations
Test Facilities
Jobs & Career
GTC
Lightning Surges
Lightning and Transient overvoltages
The origin of overvoltages
Keraunic levels
Effects of lightning
Surge Protection
Citel's VG Technology
International Standards
Products
AC Power
Photovoltaic
LED
Dataline
Radiocommunication
Telecom
GDT
Miscellaneous
Applications
Datacenter
Surge protection for LED-lighting systems
Surge protection for cell phone communication
Security Systems
Industrial Installation
Wind Turbine Installation
Photovoltaic installations
Water treatment
Surge protection for E-mobility
Gas Discharge Tubes and Gas Filled Spark Gaps
Services
Information
Selection guide
Order form
Partner
Toggle Dropdown
Contact Citel
Our partners in Europe
Privacy policy
Impress
Toggle Dropdown
News
Contact
Product ranges
AC Power
Photovoltaic
LED
Telecom
Dataline
Radiocommunication
GDT
Accessories
AC Power
Type 1+2 AC surge protector
DS504E-320
Type 1+2 AC surge protector - 3-phase+N
DS504E-320
Part Number:
504320
Type 1 + 2 multipolar AC surge protector
Iimp total : 100 kA (10/350µs impulse)
Imax : 140 kA (8/20µs impulse)
Internal disconnections, status indicator and remote signaling
Conforme NF EN 61643-11, IEC 61643-11, UL1449 ed.5
Datasheet
Installation Sheet
Tender specifications
Contact Us
The DS500E range of surge protectors are Type 1 + 2, very high power, they are intended to be installed at the entry of the Low Voltage installation. They are used to protect single-phase, three-phase or three-phase + Neutral networks in common mode or in common and differential mode. The 'Multi-Varistor' technology used allows the best possible behavior for the LV network (no follow-on current). The DS500E range is installed on a DIN Rail and has a double connection for the active conductor, which allows an optimized connection to the network.
Select another reference:
DS500E-230
DS500E-320
DS500E-400
DS502E-230
DS502E-230/G
DS502E-320
DS502E-320/G
DS502E-400
DS503E-230
DS503E-320
DS503E-400
DS504E-230
DS504E-230/G
DS504E-320
DS504E-320/G
DS504E-400
Electrical Properties
Mechanical Properties
Norms
Deconnector
Schemas
SPD type
1+2
Network
230/400 V 3-phase+N
AC system
TNS
Nominal line voltage
Un
230 Vac
Max. AC operating voltage
Uc
320 Vac
Max. load current
IL
100 A
Temporary Over Voltage (TOV) Charasteristics - 5 sec.
UT
580 Vac withstand
Temporary Over Voltage (TOV) Charasteristics - 120 mn
UT
440 Vac disconnection
Operating current
Ic
< 3 mA
Follow current
If
None
Nominal discharge current
In
50 kA
Max. discharge current
Imax
200 kA
Impulse current by pole
Iimp
50 kA
Total lightning current
Itotal
200 kA
Specific energy by pole
W/R
156 kJ/ohm
Connection mode(s)
L/PE and N/PE
Protection mode(s)
Common mode/Differential mode
Protection level N/PE
Up N/PE
1.8 kV
Protection level L/PE
Up L/PE
1.8 kV
Protection level N/PE at 5 kA
Up-5kA
1.2 kV
Residual voltage L/PE at 5 kA
Up-5kA
1.2 kV
Admissible short-circuit current
Isccr
50 000 A
Technology
MOV
SPD configuration
3-phase
Connection to Network
By screw terminals: 6-35mm² / by bus
Format
1-pole modular box assembled
Mounting
Symmetrical rail 35 mm (EN 60715)
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu
-40/+85°C
Protection rating
IP20
Failsafe mode
Disconnection from AC network
Disconnection indicator
1 mechanical indicator by pole
Remote signaling of disconnection
Output on changeover contact
Dimensions
See diagram
Standards compliance
IEC 61643-11 / EN 61643-11 / UL1449 ed.5
Certification
EAC
Thermal disconnector
Internal
Installation ground fault breaker
Type 'S' or delayed
Fuses
Fuses Type gG - 500 A
×
SPD type :
1+2
Network:
230/400 V 3-phase+N
Max. AC operating voltage :
320 Vac
Max. discharge current :
200 kA
Impulse current by pole :
50 kA
Admissible short-circuit current:
50 000 A
Technology:
MOV
SPD configuration:
3-phase
Remote signaling of disconnection:
Output on changeover contact
Standards compliance:
IEC 61643-11 / EN 61643-11 / UL1449 ed.5
Certification:
EAC
Description:
Type 1+2 AC surge protector - 3-phase+N
Read more
Read more