CITEL
Test Facilities
Jobs & Career
About us
Locations
GTC
Lightning Surges
Citel's VG Technology
International Standards
Lightning and Transient overvoltages
The origin of overvoltages
Keraunic levels
Effects of lightning
Surge Protection
Products
AC Power
Radiocommunication
Telecom
Miscellaneous
GDT
Dataline
Photovoltaic
LED
Applications
Security Systems
Wind Turbine Installation
Industrial Installation
Datacenter
Surge protection for LED-lighting systems
Photovoltaic installations
Gas Discharge Tubes and Gas Filled Spark Gaps
Surge protection for E-mobility
Surge protection for cell phone communication
Water treatment
Services
Information
Order form
Selection guide
Partner
Toggle Dropdown
Contact Citel
Privacy policy
Our partners in Europe
Impress
Toggle Dropdown
News
Contact
Product ranges
AC Power
Photovoltaic
LED
Telecom
Dataline
Radiocommunication
GDT
Accessories
AC Power
Type 1+2+3 AC surge protector
DUT250VG-300/TNS
Type 1+2+3 AC surge protector - 3-phase+N
DUT250VG-300/TNS
Part Number:
3597
Type 1+2+3, 3-phase surge protector
Common and differential mode
Very compact monobloc enclosure
Iimp by pole/total : 25kA
Internal disconnection, status indicator
Optimized to TOV
EN 61643-11, IEC 61643-11 and UL1449 ed.5 compliance
Datasheet
Installation Sheet
Tender specifications
Contact Us
The DUT250VG is a compact and heavy duty Type 1+2+3 SPD, designed to be connected at the entrance of the electrical installation, on a 3-phase 230/400 V AC network. The Spark gap + Varistor technology allows a very low level of protection and an absence of following current. The DUT250VG is a 3-phase SPD and provides a common and differential mode protection. This SPD is built in a compact enclosure for DIN rail mounting.
Select another reference:
DUT250VG-300/TNC
DUT250VG-300/TNS
DUT250VG-300/TT
DUT250VG-300/ZP/TNC
DUT250VG-300/ZP/TNS
DUT250VG-300/ZP/TT
Electrical Properties
Mechanical Properties
Norms
Deconnector
Schemas
SPD type
1+2+3
Network
230/400 V 3-phase+N
AC system
TNS
Nominal line voltage
Un
230/400 Vac
Max. AC operating voltage
Uc
255 Vac
Temporary Over Voltage (TOV) Charasteristics - 5 sec.
UT
335 Vac withstand
Temporary Over Voltage (TOV) Charasteristics - 120 mn
UT
440 Vac withstand
Residual Current
Ipe
None
Follow current
If
None
Nominal discharge current
In
40 kA
Max. discharge current
Imax
100 kA
Impulse current by pole
Iimp
25 kA
Total lightning current
Itotal
50 kA
Withstand on Combination waveform IEC 61643-11
Uoc
6 kV
Withstand on overvoltages IEEE C62.41.1
20 kV
Specific energy by pole
W/R
156 kJ/ohm
Connection mode(s)
L/N and L/PE
Protection mode(s)
Common/Differential mode
Protection level L/N
Up L/N
1.5 kV
Protection level N/PE
Up N/PE
1.5 kV
Admissible short-circuit current
Isccr
50 000 A
Technology
VG Technology (MOV+GSG)
SPD configuration
3-phase+Neutral
Connection to Network
By screw terminals: 6-35mm² / by bus
Format
Multipolar modular box
Mounting
Symmetrical rail 35 mm (EN 60715)
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu
-40/+85°C
Protection rating
IP20
Disconnection indicator
3 mechanical indicators by pole
Remote signaling of disconnection
Output on changeover contact
Dimensions
See diagram
Standards compliance
IEC 61643-11 / EN 61643-11 / UL1449 ed.5
Certification
EAC
Thermal disconnector
Internal
Installation ground fault breaker
Type 'S' or delayed
Fuses
Fuse assembly: SFD1-25-31S / or Fuses Type gG 315 A
×
Read more